Fluids / Ethylene glycol, 30 % by volume

Thermal conductivity of ethylene glycol, 30 % by volume vs temperature

Thermal conductivity in W/(m·K), from -10 to 100 °C. The chart and the table below are the same numbers; the table is the one you can copy.

Thermal conductivity W/(m·K)
Thermal conductivity of ethylene glycol, 30 % by volume in W/(m·K), from -10 to 100 °C-10 °C — 0.442 W/(m·K)0 °C — 0.45 W/(m·K)20 °C — 0.464 W/(m·K)40 °C — 0.477 W/(m·K)60 °C — 0.487 W/(m·K)80 °C — 0.494 W/(m·K)100 °C — 0.499 W/(m·K)0.4450.450.4550.460.4650.470.4750.480.4850.490.495-100102030405060708090100Temperature (°C)Thermal conductivity (W/(m·K))
Ethylene glycol, 30 % by volume — everything else at 20 °C (default)
Density1,041 kg/m³
Specific heat3.7 kJ/(kg·K)
Dynamic viscosity2.4 mPa·s
Thermal conductivity by temperature
Temperature (°C)Thermal conductivity (W/(m·K))Row
-100.442published
00.45published
100.45719interpolated
200.464published
300.47075interpolated
400.477published
500.48237interpolated
600.487published
700.49081interpolated
800.494published
900.49662interpolated
1000.499published

Rows marked published land exactly on a source anchor and are the tabulated figure. The rest are this library’s interpolation between the two anchors either side — good enough to design with, and said out loud so you can decide that for yourself.

ASHRAE Handbook—Fundamentals, Ch. 31 (Secondary Coolants), interpolated from published tables · validated -10 to 100 °C · interpolated between 7 published anchors (values held, not extrapolated, past the ends)