Fluids / Ethylene glycol, 50 % by volume

Density of ethylene glycol, 50 % by volume vs temperature

Density in kg/m³, from -30 to 100 °C. The chart and the table below are the same numbers; the table is the one you can copy.

Density kg/m³
Density of ethylene glycol, 50 % by volume in kg/m³, from -30 to 100 °C-30 °C — 1,092 kg/m³-20 °C — 1,089 kg/m³-10 °C — 1,086 kg/m³0 °C — 1,082 kg/m³20 °C — 1,072 kg/m³40 °C — 1,060 kg/m³60 °C — 1,046 kg/m³80 °C — 1,031 kg/m³100 °C — 1,015 kg/m³10201030104010501060107010801090-30-20-100102030405060708090100Temperature (°C)Density (kg/m³)
Ethylene glycol, 50 % by volume — everything else at 20 °C (default)
Specific heat3.29 kJ/(kg·K)
Dynamic viscosity4.2 mPa·s
Thermal conductivity0.389 W/(m·K)
Density by temperature
Temperature (°C)Density (kg/m³)Row
-301,092published
-201,089published
-101,086published
01,082published
101,077.3interpolated
201,072published
301,066.3interpolated
401,060published
501,053.2interpolated
601,046published
701,038.6interpolated
801,031published
901,023.1interpolated
1001,015published

Rows marked published land exactly on a source anchor and are the tabulated figure. The rest are this library’s interpolation between the two anchors either side — good enough to design with, and said out loud so you can decide that for yourself.

ASHRAE Handbook—Fundamentals, Ch. 31 (Secondary Coolants), interpolated from published tables · validated -30 to 100 °C · interpolated between 9 published anchors (values held, not extrapolated, past the ends)