Fluids / Propylene glycol, 50 % by volume

Density of propylene glycol, 50 % by volume vs temperature

Density in kg/m³, from -30 to 100 °C. The chart and the table below are the same numbers; the table is the one you can copy.

Density kg/m³
Density of propylene glycol, 50 % by volume in kg/m³, from -30 to 100 °C-30 °C — 1,062 kg/m³-20 °C — 1,058 kg/m³-10 °C — 1,055 kg/m³0 °C — 1,051 kg/m³20 °C — 1,041 kg/m³40 °C — 1,029 kg/m³60 °C — 1,016 kg/m³80 °C — 1,002 kg/m³100 °C — 987 kg/m³9901000101010201030104010501060-30-20-100102030405060708090100Temperature (°C)Density (kg/m³)
Propylene glycol, 50 % by volume — everything else at 20 °C (default)
Specific heat3.54 kJ/(kg·K)
Dynamic viscosity7.6 mPa·s
Thermal conductivity0.388 W/(m·K)
Density by temperature
Temperature (°C)Density (kg/m³)Row
-301,062published
-201,058published
-101,055published
01,051published
101,046.3interpolated
201,041published
301,035.2interpolated
401,029published
501,022.6interpolated
601,016published
701,009.1interpolated
801,002published
90994.56interpolated
100987published

Rows marked published land exactly on a source anchor and are the tabulated figure. The rest are this library’s interpolation between the two anchors either side — good enough to design with, and said out loud so you can decide that for yourself.

ASHRAE Handbook—Fundamentals, Ch. 31 (Secondary Coolants), interpolated from published tables · validated -30 to 100 °C · interpolated between 9 published anchors (values held, not extrapolated, past the ends)