Fluids / Propylene glycol, 50 % by volume

Specific heat of propylene glycol, 50 % by volume vs temperature

Specific heat in kJ/(kg·K), from -30 to 100 °C. The chart and the table below are the same numbers; the table is the one you can copy.

Specific heat kJ/(kg·K)
Specific heat of propylene glycol, 50 % by volume in kJ/(kg·K), from -30 to 100 °C-30 °C — 3.4 kJ/(kg·K)-20 °C — 3.43 kJ/(kg·K)-10 °C — 3.46 kJ/(kg·K)0 °C — 3.48 kJ/(kg·K)20 °C — 3.54 kJ/(kg·K)40 °C — 3.6 kJ/(kg·K)60 °C — 3.66 kJ/(kg·K)80 °C — 3.72 kJ/(kg·K)100 °C — 3.78 kJ/(kg·K)3.43.453.53.553.63.653.73.75-30-20-100102030405060708090100Temperature (°C)Specific heat (kJ/(kg·K))
Propylene glycol, 50 % by volume — everything else at 20 °C (default)
Density1,041 kg/m³
Dynamic viscosity7.6 mPa·s
Thermal conductivity0.388 W/(m·K)
Specific heat by temperature
Temperature (°C)Specific heat (kJ/(kg·K))Row
-303.4published
-203.43published
-103.46published
03.48published
103.5088interpolated
203.54published
303.57interpolated
403.6published
503.63interpolated
603.66published
703.69interpolated
803.72published
903.75interpolated
1003.78published

Rows marked published land exactly on a source anchor and are the tabulated figure. The rest are this library’s interpolation between the two anchors either side — good enough to design with, and said out loud so you can decide that for yourself.

ASHRAE Handbook—Fundamentals, Ch. 31 (Secondary Coolants), interpolated from published tables · validated -30 to 100 °C · interpolated between 9 published anchors (values held, not extrapolated, past the ends)