Fluids / R-410A (saturated liquid)

Thermal conductivity of R-410A (saturated liquid) vs temperature

Thermal conductivity in W/(m·K), from -40 to 60 °C along the saturation curve. The chart and the table below are the same numbers; the table is the one you can copy.

Thermal conductivity W/(m·K)
Thermal conductivity of R-410A (saturated liquid) in W/(m·K), from -40 to 60 °C-40 °C — 0.135 W/(m·K)-20 °C — 0.123 W/(m·K)0 °C — 0.111 W/(m·K)20 °C — 0.099 W/(m·K)40 °C — 0.087 W/(m·K)60 °C — 0.073 W/(m·K)0.080.090.10.110.120.13-40-30-20-100102030405060Temperature (°C)Thermal conductivity (W/(m·K))
R-410A (saturated liquid) — everything else at 20 °C (default)
Density1,046 kg/m³
Vapour pressure1,444.2 kPa
Latent heat of vaporisation202.9 kJ/kg
Dynamic viscosity0.14 mPa·s
Specific heat1.6 kJ/(kg·K)
Thermal conductivity by temperature
Temperature (°C)Thermal conductivity (W/(m·K))Row
-400.135published
-300.129interpolated
-200.123published
-100.117interpolated
00.111published
100.105interpolated
200.099published
300.093125interpolated
400.087published
500.080125interpolated
600.073published

Rows marked published land exactly on a source anchor and are the tabulated figure. The rest are this library’s interpolation between the two anchors either side — good enough to design with, and said out loud so you can decide that for yourself.

NIST REFPROP / ASHRAE Handbook—Fundamentals, Ch. 30, saturated liquid line · validated -40 to 60 °C · interpolated between 6 published anchors (values held, not extrapolated, past the ends) · saturated state only