Fluids / Ethylene glycol, 50 % by volume

Dynamic viscosity of ethylene glycol, 50 % by volume vs temperature

Dynamic viscosity in mPa·s, from -30 to 100 °C. The chart and the table below are the same numbers; the table is the one you can copy.

Dynamic viscosity mPa·s (log scale)
Dynamic viscosity of ethylene glycol, 50 % by volume in mPa·s, from -30 to 100 °C-30 °C — 50 mPa·s-20 °C — 27 mPa·s-10 °C — 15.5 mPa·s0 °C — 9.5 mPa·s20 °C — 4.2 mPa·s40 °C — 2.3 mPa·s60 °C — 1.5 mPa·s80 °C — 1.05 mPa·s100 °C — 0.8 mPa·s110-30-20-100102030405060708090100Temperature (°C)Dynamic viscosity (mPa·s (log scale))
Ethylene glycol, 50 % by volume — everything else at 20 °C (default)
Density1,072 kg/m³
Specific heat3.29 kJ/(kg·K)
Thermal conductivity0.389 W/(m·K)
Dynamic viscosity by temperature
Temperature (°C)Dynamic viscosity (mPa·s)Row
-3050published
-2027published
-1015.5published
09.5published
106.1696interpolated
204.2published
303.0334interpolated
402.3published
501.8291interpolated
601.5published
701.2429interpolated
801.05published
900.91167interpolated
1000.8published

Rows marked published land exactly on a source anchor and are the tabulated figure. The rest are this library’s interpolation between the two anchors either side — good enough to design with, and said out loud so you can decide that for yourself.

ASHRAE Handbook—Fundamentals, Ch. 31 (Secondary Coolants), interpolated from published tables · validated -30 to 100 °C · interpolated between 9 published anchors (values held, not extrapolated, past the ends)