R (h⋅ft2⋅∘F/BTU)\text{R (h}{\cdot}\text{ft}^{2}{\cdot}^{\circ}\text{F/BTU)}

hour square foot Fahrenheit per BTU

Areal thermal resistanceexact by definition

The R-value is the customary US and Canadian imperial measure of insulating performance, in hour square foot Fahrenheit degrees per BTU: how many hours, square feet and degrees of difference it takes to pass one BTU. One imperial R equals 0.176110 m²·K/W, a relation exact by definition from the International Table BTU, the international foot and the 5/9 Fahrenheit degree, though the decimal shown is a rounding of that exact ratio. Higher is better, and R-values of layers in series add.

Watch out: The imperial R-value and the metric RSI differ by a factor of about 5.678, and insulation in Canada is sold with both printed on the bag. R-20 is RSI 3.52. Beyond that, a batt's rated R is the R of the batt alone: once studs, plates and headers are counted, the effective R of the assembly is typically 10 to 25 percent lower, because wood conducts far better than fibreglass. Codes that regulate effective R are asking for the assembly value, not the label value.

1 R (h⋅ft2⋅∘F/BTU)\text{R (h}{\cdot}\text{ft}^{2}{\cdot}^{\circ}\text{F/BTU)} 0.17611018 RSI (m2⋅K/W)\text{RSI (m}^{2}{\cdot}\text{K/W)}
Where the unit came from

The R-value became the North American consumer label for insulation because it turns a material property into a single number that adds up. The US Federal Trade Commission's R-value Rule requires it on insulation packaging and in advertising, which is why every batt in a hardware store carries one.

About the hour square foot fahrenheit per btu

An R-value is a thermal resistance per unit area, and the definition is worth spelling out because the unit looks like alphabet soup: R=ΔT⋅A/QR = \Delta T \cdot A / Q, with ΔT\Delta T in Fahrenheit degrees, AA in square feet, and QQ in BTU per hour. So R-20 means that one square foot of the assembly passes one BTU per hour for every 20 Fahrenheit degrees across it. Turn it upside down and you get the U-value: U=1/RU = 1/R, in BTU/(h·ft²·°F), which is what windows are rated in.

Two properties make the R-value useful. Layers in series add, so drywall (R-0.45) plus R-20 batt plus sheathing (R-1.3) plus siding gives a nominal total you can just sum. And heat loss is then Q=AΔT/RQ = A \Delta T / R, so a 1000 ft² wall at R-20 with 60 F° across it loses 1000×60/20=30001000 \times 60/20 = 3000 BTU/h.

Two things routinely go wrong. First, the label R and the assembly R are different numbers. A 2x6 wall with R-20 batts is maybe R-16 effective once the framing is counted, because the studs are R-1.25 per inch against the insulation's R-3.2 and they occupy 20 to 25 percent of the wall. Continuous exterior insulation exists mostly to fix that. Second, the metric confusion: RSI 3.52 and R-20 are the same wall, and the ratio between the two units is 5.678. An imported specification quoting "R 3.5" is almost certainly RSI and describes a wall six times better than an imperial R-3.5 sheet of foam.

One hour square foot fahrenheit per btu in every areal thermal resistance unit

176,110square millimeter kelvin per watt (mm²·K/W)
1,761.1square centimeter Celsius per watt (cm²·°C/W)
144square inch hour Fahrenheit per BTU (in²·h·°F/BTU)
1.7611tog (tog)
1.13619clo (clo)
1hour square foot Fahrenheit per BTU (R (h·ft²·°F/BTU))this unit
0.204679square meter hour Celsius per kilocalorie (m²·h·°C/kcal)
0.17611square meter kelvin per watt (RSI (m²·K/W))
0.17611square meter Celsius per watt (m²·°C/W)
Convert hour square foot fahrenheit per btu to
rvalue → rsi

All areal thermal resistance units →