U-Factor from Total R-Value (U = 1/R)
Also known as U value from R value
Enter your known values, leave one input blank, and solves for the missing one. Try different units for next level excitement!
Learning zone
Insulation is sold by resistance and windows are sold by conductance, so the same envelope gets described two ways: R-20 is U-0.05 in imperial units, and RSI 3.52 is U = 0.284 W/(m²·K) in metric. They are reciprocals of each other within one unit system — and note that the conversion between systems is the same 5.678 factor running the other way, since U in W/(m²·K) equals 5.678 divided by the imperial R. Codes mix the two deliberately: opaque assemblies get a prescriptive R, fenestration gets a U-factor on the NFRC label, and the compliance path adds them up as UA products.
Here is the mistake that costs real money, and it appears in spreadsheets everywhere: U-factors add, R-values add, but never in the same direction. R-values add along the path heat takes, in series through the layers. U-factors add across the wall, area-weighted, when parallel paths share the same ΔT — which is why a wall and its windows combine as ΣUA and not as an average R. Averaging R-values across an elevation of wall and glass gives a wall that looks far better than it is: 90% at R-20 and 10% at R-3 does not average to R-18.3; it averages to U = 0.9 × 0.05 + 0.1 × 0.333 = 0.0783, which is R-12.8. The glass ate a third of the wall's performance, and only the U-side arithmetic showed it.
- = U-factor
- = Total assembly R-value
- U-factor — Newton's Law of Cooling (Q = hAΔT), Overall Heat Transfer Coefficient (U)
- Total assembly R-value — Total R-Value of an Assembly, Heat Loss Through an Assembly (Q = A·ΔT/R)