Total R-Value of an Assembly
Also known as wall R value · RSI total
Worked example: RSI 3.52 wall less 0.12 film and 0.08 gypsum → cavity RSI 3.32 — press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Try different units for next level excitement!
Stacking the wall →
UniversityThermodynamics & Heat Transfer
Test your skills in the Exam Room: new numbers every attempt — free lessons for students, no sign-up, just pure learning. Find 1 more lesson on this formula.
share your results
Total R-Value of an Assembly explained
Because every layer of a wall passes the same heat through the same square metre, their R-values add: . Set an unused layer to zero. A conventional 2×6 wall totals R-19 in the cavity, R-5 for an inch of exterior polyiso and about R-1.13 for the inside air film plus gypsum, giving R-25.13 — and note that the two "small" layers together are 24% of the answer, which is why the air films and finishes are in the ASHRAE tables at all rather than being waved away. In metric the same sum runs RSI 0.12 for the inside film, 3.32 of cavity and 0.08 for drywall to make RSI 3.52, the Canadian code number that everyone quotes as R-20.
Two things do not belong in this sum. Airspaces are not insulation in proportion to their thickness: a sealed 20 mm cavity is worth about RSI 0.17 (R-1) and a 100 mm one is worth barely more, because convection takes over as soon as the gap is wide enough to circulate — the exception is a low-emissivity foil facing the gap, which doubles it. And the exterior air film depends on wind, dropping from RSI 0.12 in still air to 0.03 in a 25 km/h breeze, so any R-value quoted with a generous outdoor film is quoting a calm day. The rule to hold on to is that only series layers add. Studs, joists and fasteners run alongside the insulation rather than behind it, and that is a parallel path, handled on the effective R-value page.
Total R-Value of an Assembly formula
- = Total assembly R-value (RSI (m²·K/W))
- = First layer R-value (RSI (m²·K/W))
- = Second layer R-value (RSI (m²·K/W))
- = Third layer R-value (RSI (m²·K/W))
Missing one of these? Work it out first, then come back
- Total assembly R-value — U-Factor from Total R-Value (U = 1/R), Heat Loss Through an Assembly (Q = A·ΔT/R)
- First layer R-value — R-Value of an Insulation Layer (R = L/k), U-Factor from Total R-Value (U = 1/R)
- Second layer R-value — R-Value of an Insulation Layer (R = L/k), U-Factor from Total R-Value (U = 1/R)
- Third layer R-value — R-Value of an Insulation Layer (R = L/k), U-Factor from Total R-Value (U = 1/R)