Stream Duty from Mass Flow (Q = ṁcΔT)

Q˙=m˙ cp ΔT\dot{Q} = \dot{m} \, c_p \, \Delta T

or type the values yourself

sig figs

Worked example: 2.5 kg/s water, cp 4186, 12 K → 125.58 kW. Press Try an example to run it live, then adjust anything.

Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.

Where Stream Duty from Mass Flow (Q = ṁcΔT) fits

Missing an input?
Your answer feeds

See also

Heat Exchanger Duty (Q = U·A·F·LMTD): Both use stream duty.Heat Exchanger Effectiveness (ε = Q/Qmax): Both use stream duty.
Here the solver did the work. Could you?

Rating the exchanger →

UniversityThermodynamics & Heat Transfer

Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning. Find 1 more lesson on this formula.

See your Report Card
Learning zone

Stream Duty from Mass Flow (Q = ṁcΔT) explained

ṁcpQΔT

Every exchanger calculation has two halves that must agree. The transfer side says Q̇ = UAF·ΔTlm\Delta T_{\mathrm{lm}}; the process side says Q̇ = ṁcₚΔT for each stream. Write both, set them equal, and the whole problem closes. Because the heat leaving the hot stream must arrive in the cold one, ṁcₚΔT for the hot side equals ṁcₚΔT for the cold side, so the stream with the smaller ṁcₚ, the smaller heat capacity rate, always shows the larger temperature swing. That single observation lets you sanity-check a datasheet from across the room: if both streams change by the same amount, their capacity rates are equal.

Worked example: 2.5 kg/s of water (cₚ = 4186 J/(kg·K)) heated 12 K takes 2.5 × 4186 × 12 = 125.6 kW. In North American units the same physics reads 500,000 BTU/h into 20,000 lb/h of oil at cₚ = 0.5 across 50 °F. Traps: cₚ is not constant. Water is flat enough to ignore, but oils and glycols vary 10–20% over a working range, so use the value at the mean temperature. And this equation is sensible heat only; the moment anything boils or condenses, the temperature stops moving and you need ṁ times the latent heat instead.

Stream Duty from Mass Flow (Q = ṁcΔT) formula

Q˙=m˙ cp ΔT\dot{Q} = \dot{m} \, c_p \, \Delta T
Where
  • Q˙\dot{Q}= Stream duty (kW)
  • m˙\dot{m}= Mass flow rate (kg/h)
  • cpc_p= Specific heat (J/(kg·K))
  • ΔT\Delta T= Temperature change (C°)
Revised 16 October 2026
Cite this page

formula.expert. (2026, October 16). Stream Duty from Mass Flow (Q = ṁcΔT) Formula & Calculator. https://formula.expert/solvers/heat-exchanger-stream-duty