Condenser Water Flow Rate
Also known as 3 GPM per ton
Worked example: 250 kW, HRF 1.2, 15 L/s → 4.785 K range. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.
Where Condenser Water Flow Rate fits
- Refrigeration capacity and efficiency6 formulas
See also
Hydronic Heat Transfer (Water): Both use condenser water flow and condenser water ΔT.Chiller Heat Rejection: Both use heat rejection factor.Glycol Loop Heat Transfer (Capacity Derate): Both use condenser water ΔT.Chiller Efficiency (kW per Ton): Both use evaporator load.Energy Efficiency Ratio (EER): Both use evaporator load.Refrigerant Mass Flow Rate: Both use evaporator load.Condenser duty →
UniversityFluid Mechanics, HVAC & Refrigeration
Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning. Find 1 more lesson on this formula.
Condenser Water Flow Rate explained
A cooling tower has to dump more heat than the building put into the chilled water, because the compressor's own electrical input ends up in the refrigerant too. The heat rejection factor accounts for that: about 1.25 for a typical electric chiller (12,000 BTU/hr of cooling plus roughly 3,000 BTU/hr of compressor work = 15,000 BTU/hr rejected per ton), 1.15–1.20 for a very efficient machine, and 1.7–1.8 for an absorption chiller, which is why absorption towers are so much larger.
Run one ton through the arithmetic at a 10 °F tower range: 15,000 ÷ (500 × 10) = 3.0 gpm, and there is the industry's favourite rule, 3 gpm per ton, standing on ASHRAE's 85 °F/95 °F condenser design. Widen the range to 15 °F and you need only 2 gpm per ton, which saves pump horsepower but costs tower approach; that trade-off is the whole subject of variable-flow condenser design. On the water-treatment side, ΔT and flow set the cycles of concentration you can hold: every 10 °F of range evaporates roughly 1 % of the circulating flow, so a 300 gpm tower at 10 °F range boils off about 3 gpm and must be bled and inhibited accordingly, or the tubes scale and the approach quietly walks away from you.
Condenser Water Flow Rate formula
- = Condenser water flow (L/min)
- = Evaporator (cooling) load (W)
- = Heat rejection factor
- = Condenser water ΔT (C°)
Cite this page
formula.expert. (2026, October 31). Condenser Water Flow Rate Formula & Calculator. https://formula.expert/solvers/condenser-water-flow-rate