Condenser Water Flow Rate

Also known as 3 GPM per ton

V˙=Q˙⋅HRFρwcw ΔT\dot{V} = \frac{\dot{Q} \cdot \mathrm{HRF}}{\rho_w c_w \, \Delta T}
sig figs

Worked example: 250 kW, HRF 1.2, 15 L/s → 4.785 K range. Press Try an example to run it live, then adjust anything.

Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.

Where Condenser Water Flow Rate fits

Your answer feeds
In this toolkit

See also

Hydronic Heat Transfer (Water): Both use condenser water flow and condenser water ΔT.Chiller Heat Rejection: Both use heat rejection factor.Glycol Loop Heat Transfer (Capacity Derate): Both use condenser water ΔT.Chiller Efficiency (kW per Ton): Both use evaporator load.Energy Efficiency Ratio (EER): Both use evaporator load.Refrigerant Mass Flow Rate: Both use evaporator load.
1 more relatedTons of Refrigeration from BTU/hr: Both use evaporator load.
Here the solver did the work. Could you?

Condenser duty →

UniversityFluid Mechanics, HVAC & Refrigeration

Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning. Find 1 more lesson on this formula.

See your Report Card
Learning zone

Condenser Water Flow Rate explained

HRFQV̇ΔT

A cooling tower has to dump more heat than the building put into the chilled water, because the compressor's own electrical input ends up in the refrigerant too. The heat rejection factor accounts for that: about 1.25 for a typical electric chiller (12,000 BTU/hr of cooling plus roughly 3,000 BTU/hr of compressor work = 15,000 BTU/hr rejected per ton), 1.15–1.20 for a very efficient machine, and 1.7–1.8 for an absorption chiller, which is why absorption towers are so much larger.

Run one ton through the arithmetic at a 10 °F tower range: 15,000 ÷ (500 × 10) = 3.0 gpm, and there is the industry's favourite rule, 3 gpm per ton, standing on ASHRAE's 85 °F/95 °F condenser design. Widen the range to 15 °F and you need only 2 gpm per ton, which saves pump horsepower but costs tower approach; that trade-off is the whole subject of variable-flow condenser design. On the water-treatment side, ΔT and flow set the cycles of concentration you can hold: every 10 °F of range evaporates roughly 1 % of the circulating flow, so a 300 gpm tower at 10 °F range boils off about 3 gpm and must be bled and inhibited accordingly, or the tubes scale and the approach quietly walks away from you.

Condenser Water Flow Rate formula

V˙=Q˙⋅HRFρwcw ΔT\dot{V} = \frac{\dot{Q} \cdot \mathrm{HRF}}{\rho_w c_w \, \Delta T}
Where
  • V˙\dot{V}= Condenser water flow (L/min)
  • Q˙\dot{Q}= Evaporator (cooling) load (W)
  • HRF\mathrm{HRF}= Heat rejection factor
  • ΔT\Delta T= Condenser water ΔT (C°)
Revised 31 October 2026
Cite this page

formula.expert. (2026, October 31). Condenser Water Flow Rate Formula & Calculator. https://formula.expert/solvers/condenser-water-flow-rate