Heat Rejected by a Power Plant (from the Electric Output and the Thermal Efficiency)
Also known as waste heat from a power plant · heat to the cooling water · heat rejected to the river · cooling tower load of a power plant · reactor waste heat · heat sent to the condenser · thermal discharge of a power plant · rejected heat for an electric output · power plant thermal pollution · Qout of a heat engine in watts
Worked example: 980 MW of nuclear electricity at the 2025 fleet efficiency 0.3267 → 2 019.69 MW rejected. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.
Where Heat Rejected by a Power Plant (from the Electric Output and the Thermal Efficiency) fits
Heat Rejected by a Power Plant (from the Electric Output and the Thermal Efficiency) explained
A thermal plant, whether coal, gas, nuclear or biomass, turns only a fraction of the heat it makes into electricity. By the first law all the rest leaves as waste heat, into a river, a lake, the sea or the air through cooling towers. For an electric output at efficiency , the heat input is , and the heat rejected is that less , which is . It is the bookkeeping of one balance: heat in equals electricity out plus heat rejected.
Read the answer through the factor . At an efficiency of one third the plant rejects twice as much heat as it sends out as electricity: 1 000 MW of electricity goes with 2 000 MW of heat to the water. A plant with an efficiency above one half rejects less heat than the electricity it makes. The formula says how much heat, not where it goes; the cooling water's temperature rise follows from the flow it is given.
The page's example uses a published input. The EIA's average operating heat rate of nuclear plants in 2025 is 10 443 Btu per kilowatt-hour (Electric Power Annual, Table 8.1), which is an efficiency of . A plant sending out 980 MW of electricity then needs MW of heat and rejects 2 019.69 MW. The same table lists 2025 coal at 10 647 and natural gas at 7 781 Btu per kilowatt-hour, and each turns into an efficiency the same way.
Backwards works too. If 2 000 MW is rejected for 1 000 MW sent out, the heat in is 3 000 MW and . With 3 000 MW in, 980 MW out as electricity and 2 020 MW rejected, . The efficiency has to lie between 0 and 1.
Heat Rejected by a Power Plant (from the Electric Output and the Thermal Efficiency) formula
- = Heat rejected (MW)
- = Electric output (MW)
- = Thermal efficiency
- U.S. Energy Information Administration, Electric Power Annual, Table 8.1, Average Operating Heat Rate for Selected Energy Sources, 2015 through 2025 (US federal work, public domain): 2025 coal 10 647, natural gas 7 781 and nuclear 10 443 Btu per kilowatt-hour, read 23 Oct 2026. Read it
Cite this page
formula.expert. (2026, October 30). Heat Rejected by a Power Plant (from the Electric Output and the Thermal Efficiency) Calculator. https://formula.expert/solvers/plant-heat-rejection