t=mcapC Qt = \frac{m_{\text{cap}}}{C \, Q}
sig figs

Worked example: 200 mg/L, 10 L/min, 7 days → 20.16 kg capacity needed. Press Try an example to run it live, then adjust anything.

Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.

Where Days Between Softener Regenerations fits

Missing an input?
In this toolkit

See also

Softener Resin Volume Required: Both use rated capacity as CaCO₃.Grains per Gallon ↔ ppm Hardness: Both use raw water hardness as CaCO₃.Hardness Load Removed per Regeneration: Both use raw water hardness as CaCO₃.Hardness Removal Efficiency and Leakage: Both use raw water hardness as CaCO₃.Soda Ash Dose for Softening (as CaCO₃): Both use raw water hardness as CaCO₃.Total Hardness as CaCO₃: Both use raw water hardness as CaCO₃.
Here the solver did the work. Could you?

Sizing the softener →

UniversityProcess & Water Chemistry

Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning. Find 1 more lesson on this formula.

See your Report Card
Learning zone

Days Between Softener Regenerations explained

CQmcapt

This is the number the customer actually feels: how often the softener wakes up at 2 a.m. and how much salt the bag loses each month. Divide the bed's rated capacity by the hardness load per unit of water and you get the run length. Working it in trade units, a 30,000 grain softener on 10 gpg water fed at 1 gallon per minute exhausts after 3,000 gallons, which is 3,000 minutes or about 50 hours of continuous flow; on typical residential intermittent use at 300 gallons a day that same bed runs 10 days. Metered control valves do exactly this arithmetic internally, which is why programming them requires an accurate hardness number and an honest household size.

The published capacity is the trap. A cubic foot of standard 8% cross-linked resin holds about 32,000 grains at a heavy 15 lb/ft³ salt dose, but only about 20,000 grains at an economical 6 lb/ft³, and the rated number on the box is almost always the high-salt figure. Size the interval on the salt setting you actually intend to run. Two more field rules: never let a bed go longer than about 14 days between regenerations regardless of capacity, because stagnant resin fouls biologically, and set the reserve capacity so the valve regenerates before the day's demand rather than during it.

Days Between Softener Regenerations formula

t=mcapC Qt = \frac{m_{\text{cap}}}{C \, Q}
Where
  • tt= Time between regenerations (s)
  • mcapm_{\text{cap}}= Rated capacity as CaCO₃ (kg)
  • CC= Raw water hardness as CaCO₃ (mg/L)
  • QQ= Average water usage (L/min)
Where this comes from

Worked from first principles: a definition, a balance or unit arithmetic, so it needs no outside source.

Revised 16 October 2026