Air Latent Heat (0.68 Rule)

Also known as 0.68 formula · latent cooling load

Q˙l=ρaV˙hfg ΔW\dot{Q}_l = \rho_a \dot{V} h_{fg} \, \Delta W
sig figs

Worked example: 0.68 rule: 2000 cfm dropping 30 gr/lb → 40,800 BTU/hr. Press Try an example to run it live, then adjust anything.

Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.

Where Air Latent Heat (0.68 Rule) fits

Missing an input?
Your answer feeds
In this toolkit

See also

Sensible Heat Ratio (SHR): Both use latent heat rate.Air Sensible Heat (1.08 Rule): Both use air volume flow.Air Total Heat (4.5 Rule): Both use air volume flow.Fan Affinity Law: Airflow vs Speed: Both use air volume flow.Fan Brake Horsepower: Both use air volume flow.Round Duct Air Velocity: Both use air volume flow.
Here the solver did the work. Could you?

The three air rules →

UniversityFluid Mechanics, HVAC & Refrigeration

Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning.

See your Report Card
Learning zone

Air Latent Heat (0.68 Rule) explained

V̇ΔWQl

Latent heat is the energy a coil spends condensing water vapour out of the air, and it never shows on a thermometer: the leaving air can be the same temperature and vastly drier. The physics is ṁair × hfg × ΔW, where ΔW is the humidity ratio change (mass of water per mass of dry air) and hfg ≈ 1060 BTU/lb (2.466 MJ/kg) at coil conditions. That gives the North American shortcut 0.68 = 60 min/hr × 0.075 lb/ft³ × 1060 BTU/lb ÷ 7000 grains/lb, which rounds 0.681 down to two digits.

Because there is no grains-per-pound unit in the picker, enter ΔW as a mass ratio: divide grains per pound by 7,000, so 1 gr/lb = 142.86 ppm = 0.014286 %, and metric users can enter g/kg directly as 1 g/kg = 0.1 %. A 2,000 cfm coil dropping the air 30 gr/lb (0.4286 %) removes 0.68 × 2,000 × 30 ≈ 40,800 BTU/hr of latent load. The classic trap is oversizing: a big compressor satisfies the thermostat in six minutes, never runs long enough to wet the coil, and leaves a clammy 74 °F house at 65 % RH, the reason ASHRAE cares more about run time than raw tonnage. Sanity check your answer against the condensate pail: 12,000 BTU/hr of latent removal is about 1.3 US gallons of water per hour.

Air Latent Heat (0.68 Rule) formula

Q˙l=ρaV˙hfg ΔW\dot{Q}_l = \rho_a \dot{V} h_{fg} \, \Delta W
Where
  • Q˙l\dot{Q}_l= Latent heat rate (W)
  • V˙\dot{V}= Airflow (L/min)
  • ΔW\Delta W= Humidity ratio change (g/kg)
Revised 16 October 2026
Cite this page

formula.expert. (2026, October 16). Air Latent Heat (0.68 Rule) Formula & Calculator. https://formula.expert/solvers/air-latent-heat