Air Latent Heat (0.68 Rule)
Also known as 0.68 formula · latent cooling load
Enter your known values, leave one input blank, and solves for the missing one. Try different units for next level excitement!
Learning zone
Latent heat is the energy a coil spends condensing water vapour out of the air, and it never shows on a thermometer — the leaving air can be the same temperature and vastly drier. The physics is ṁair × hfg × ΔW, where ΔW is the humidity ratio change (mass of water per mass of dry air) and hfg ≈ 1060 BTU/lb (2.466 MJ/kg) at coil conditions. That gives the North American shortcut 0.68 = 60 min/hr × 0.075 lb/ft³ × 1060 BTU/lb ÷ 7000 grains/lb, which rounds 0.681 down to two digits.
Because there is no grains-per-pound unit in the picker, enter ΔW as a mass ratio: divide grains per pound by 7,000, so 1 gr/lb = 142.86 ppm = 0.014286 %, and metric users can enter g/kg directly as 1 g/kg = 0.1 %. A 2,000 cfm coil dropping the air 30 gr/lb (0.4286 %) removes 0.68 × 2,000 × 30 ≈ 40,800 BTU/hr of latent load. The classic trap is oversizing: a big compressor satisfies the thermostat in six minutes, never runs long enough to wet the coil, and leaves a clammy 74 °F house at 65 % RH — the reason ASHRAE cares more about run time than raw tonnage. Sanity check your answer against the condensate pail: 12,000 BTU/hr of latent removal is about 1.3 US gallons of water per hour.
- = Latent heat rate
- = Airflow
- = Humidity ratio change
- Latent heat rate — Air Total Heat (4.5 Rule), Hydronic Heat Transfer (Water)
- Airflow — Air Sensible Heat (1.08 Rule), Air Total Heat (4.5 Rule)