Air Sensible Heat (1.08 Rule)
Also known as 1.08 formula · CFM delta T · sensible cooling load
Enter your known values, leave one input blank, and solves for the missing one. Try different units for next level excitement!
Learning zone
This is the water formula wearing a different hat: mass flow times specific heat times temperature change, with air's properties instead of water's. Standard air weighs 0.075 lb/ft³ (1.2014 kg/m³) and holds 0.240 BTU/(lb·°F), so 1.08 = 60 min/hr × 0.075 lb/ft³ × 0.240 BTU/(lb·°F). A furnace moving 1,000 cfm across a 20 °F rise delivers 1.08 × 1,000 × 20 = 21,600 BTU/hr, which this page returns as 6.33 kW.
Two traps. First, "standard air" means roughly 70 °F at sea level — at Denver's 5,300 ft the density drops about 18 %, so the constant falls to about 0.89 and a rooftop unit sized on 1.08 quietly under-delivers. Second, this is sensible heat only: it says nothing about the moisture the coil pulls out, which on a humid August afternoon can be a third of the total load. Balancing technicians run the formula backwards constantly — measure supply and return temperature at a known airflow, and you have the delivered capacity without opening a single panel.
- = Sensible heat rate
- = Airflow
- = Dry-bulb ΔT
- Sensible heat rate — Air Total Heat (4.5 Rule), Hydronic Heat Transfer (Water)
- Airflow — Air Latent Heat (0.68 Rule), Air Total Heat (4.5 Rule)
- Dry-bulb ΔT — Hydronic Heat Transfer (Water), Glycol Loop Heat Transfer (Capacity Derate)