Air Sensible Heat (1.08 Rule)
Also known as 1.08 formula · CFM delta T · sensible cooling load
Worked example: 1.08 rule: 1000 cfm at 20 dF → 21,600 BTU/hr. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.
Where Air Sensible Heat (1.08 Rule) fits
- The HVAC heat transfer constants6 formulas
See also
Sensible Heat Ratio (SHR): Both use sensible heat rate.Air Latent Heat (0.68 Rule): Both use air volume flow.Air Total Heat (4.5 Rule): Both use air volume flow.Fan Affinity Law: Airflow vs Speed: Both use air volume flow.Fan Brake Horsepower: Both use air volume flow.Round Duct Air Velocity: Both use air volume flow.The three air rules →
UniversityFluid Mechanics, HVAC & Refrigeration
Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning. Find 2 more lessons on this formula.
Air Sensible Heat (1.08 Rule) explained
This is the water formula wearing a different hat: mass flow times specific heat times temperature change, with air's properties instead of water's. Standard air weighs 0.075 lb/ft³ (1.2014 kg/m³) and holds 0.240 BTU/(lb·°F), so 1.08 = 60 min/hr × 0.075 lb/ft³ × 0.240 BTU/(lb·°F). A furnace moving 1,000 cfm across a 20 °F rise delivers 1.08 × 1,000 × 20 = 21,600 BTU/hr, which this page returns as 6.33 kW.
Two traps. First, "standard air" means roughly 70 °F at sea level: at Denver's 5,300 ft the density drops about 18 %, so the constant falls to about 0.89 and a rooftop unit sized on 1.08 quietly under-delivers. Second, this is sensible heat only: it says nothing about the moisture the coil pulls out, which on a humid August afternoon can be a third of the total load. Balancing technicians run the formula backwards constantly: measure supply and return temperature at a known airflow, and you have the delivered capacity without opening a single panel.
Air Sensible Heat (1.08 Rule) formula
- = Sensible heat rate (W)
- = Airflow (L/min)
- = Dry-bulb ΔT (C°)
Cite this page
formula.expert. (2026, October 16). Air Sensible Heat (1.08 Rule) Formula & Calculator. https://formula.expert/solvers/air-sensible-heat