Condensate Return Percentage
Also known as percent condensate returned
Worked example: 6000 lb/h returned of 10,000 lb/h steam → 60%. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.
Where Condensate Return Percentage fits
- The boiler water balance8 formulas
See also
Boiler Makeup from Condensate Return: Both use condensate return percentage and steam production rate.Flash Steam Mass Rate: Both use condensate returned.Steam Coil Condensate Load: Both use condensate returned.Boiler Blowdown Rate from Steam Rate: Both use steam production rate.Boiler Horsepower to Steam Rate: Both use steam production rate.Desuperheater Water Injection Rate: Both use steam production rate.Condensate comes home →
UniversityProcess & Water Chemistry
Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning. Find 1 more lesson on this formula.
Condensate Return Percentage explained
Condensate is the best boiler feedwater on the planet: distilled, near zero hardness, near zero dissolved solids, and already sitting at 180–200 °F. Returning 6000 lb/h out of 10,000 lb/h generated is 60% return, and every point you add cuts fuel, makeup water, softener salt, chemical and blowdown together. A closed process plant can hit 90%; a hospital with steam humidifiers and sterilisers may never exceed 40% because much of the steam is consumed rather than condensed.
The number is also a leak detector. Return percentage falling from 75% to 55% over a season almost always means failed steam traps blowing live steam to the vent, or a buried return line leaking into the ground, and the makeup meter will confirm it. The caution on the treatment side is that returned condensate is not automatically good condensate: it picks up carbonic acid from CO₂ released by feedwater alkalinity, and that acid eats grooves along the bottom of return lines. If your return conductivity or iron suddenly spikes, dump the condensate to drain until you find the process leak or the corrosion source, rather than feeding it to the boiler.
Condensate Return Percentage formula
- = Condensate return percentage (%)
- = Condensate returned (kg/h)
- = Steam production rate (kg/h)
Worked from first principles: a definition, a balance or unit arithmetic, so it needs no outside source.