Cooling Tower Evaporation Rate

Also known as evaporation loss · 1 percent per 10 degrees

E=0.001 R ΔTE = 0.001 \, R \, \Delta T
sig figs

Worked example: 600 m3/h losing 90 L/min → 5 degC range. Press Try an example to run it live, then adjust anything.

Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.

Where Cooling Tower Evaporation Rate fits

Missing an input?
Your answer feeds
In this toolkit

See also

Cooling Tower Heat Rejection: Both use recirculation rate and cooling range.Blowdown Rate from Cycles: Both use evaporation rate.Cooling Tower Makeup Water Rate: Both use evaporation rate.Cooling Tower Range: Both use cooling range.Cooling Tower Drift Loss: Both use recirculation rate.System Volume from Turnover Time: Both use recirculation rate.
Here the solver did the work. Could you?

Tower water balance →

UniversityFluid Mechanics, HVAC & Refrigeration

Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning. Find 3 more lessons on this formula.

See your Report Card
Learning zone

Cooling Tower Evaporation Rate explained

ERΔT

Rejecting heat by evaporation costs about one percent of the circulating water for every ten Fahrenheit degrees of range: the arithmetic behind the constant 0.001. It falls straight out of an energy balance: to drop a pound of water by 10 °F you must remove 10 BTU, and boiling off a pound of water at tower temperatures absorbs roughly 1000 BTU, so one pound in a hundred leaves as vapour. A 1000 gpm tower on a standard 10 °F range therefore evaporates about 10 gpm, or 14,400 gallons a day. The solver applies the rule per Fahrenheit degree even when you enter the range in Celsius, converting for you.

The rule is deliberately blunt and it is honest about it: real evaporation varies with ambient wet bulb, because in cold, dry weather part of the heat leaves as sensible warming of the air rather than as latent heat. Field factors of 0.00085 in winter and 0.00110 on a humid summer afternoon bracket the reality, so treat the 0.001 answer as a design-day figure. The common mistake is applying it to a closed-circuit or dry cooler: those lose no water at all, and a technician who bills a dry cooler for makeup has some explaining to do.

Cooling Tower Evaporation Rate formula

E=0.001 R ΔTE = 0.001 \, R \, \Delta T
Where
  • EE= Evaporation rate (L/min)
  • RR= Recirculation rate (L/min)
  • ΔT\Delta T= Cooling range (C°)
Where this comes from

Worked from first principles: a definition, a balance or unit arithmetic, so it needs no outside source.

Revised 16 October 2026
Cite this page

formula.expert. (2026, October 16). Cooling Tower Evaporation Rate Formula & Calculator. https://formula.expert/solvers/cooling-tower-evaporation-rate