Steam Coil Condensate Load
Also known as condensate load · steam trap sizing · steam coil steam rate · pounds of steam per hour · trap load
or type the values yourself
Worked example: A 210 kW coil on steam of 2,100 kJ/kg condenses 0.1 kg/s = 360 kg/h. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.
Where Steam Coil Condensate Load fits
- h_fgFluids table
See also
Air Sensible Heat (1.08 Rule): Where the coil duty comes from on the air sideSaturation Temperature and Pressure of Steam: The coil pressure sets the temperature, and with it the latent heatFlash Steam Mass Rate: What this condensate does when it reaches a lower pressureCondensate Return Percentage: Both use condensate load.Flash Steam Percentage: Both use latent heat at coil pressure.Jakob Number: Both use latent heat at coil pressure.Steam losses and loads →
UniversityThermodynamics & Heat Transfer
Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning.
Steam Coil Condensate Load explained
A steam coil does its work by condensing, so the steam it eats is simply the duty divided by the latent heat at the pressure the coil is running at. A 150 kW preheat coil fed 15 psig steam, where is about 2,199 kJ/kg, condenses 150/2,199 = 0.0682 kg/s, which is 246 kg/h or roughly 540 lb/h. Notice that the answer is not really a flow of steam so much as a flow of water: everything that condenses has to leave through the trap, which is why the same number is called the condensate load and why it is the figure the trap, the return line and the receiver all get sized from.
The pressure matters twice over and in opposite directions. Raising it gives a hotter coil and a bigger temperature difference, so the coil transfers more heat per square foot, but it also LOWERS the latent heat each kilogram carries, so the mass flow climbs faster than the duty does. That is the trade-off behind every steam coil selection.
Then there is the number this page does not give you, and it is the one that matters on a cold morning. The running load calculated here is a steady-state figure. Start-up is worse, sometimes far worse: the coil metal is cold, the air on it is cold, and condensate forms faster than the coil will ever produce it once warm. Traps are selected on two to three times the running load for that reason. Undersize the trap and condensate backs up into the tubes, where it subcools, and in a coil facing outdoor air in a Canadian winter it freezes and splits them, which is exactly why steam-distributing "non-freeze" coils exist, with an inner perforated tube that keeps live steam against the full length of the outer tube instead of letting a stalled slug sit in the bottom.
Steam Coil Condensate Load formula
- = Condensate load (kg/h)
- = Coil duty (W)
- = Latent heat at coil pressure (J/kg)
Cite this page
formula.expert. (2026, October 30). Steam Coil Condensate Load Formula & Calculator. https://formula.expert/solvers/steam-coil-condensate-load