Expansion Tank Acceptance Volume
Also known as expansion tank size · acceptance volume
Worked example: 4000 L loop, 250 L tank, 180/300 kPa abs → e = 2.5%. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.
Where Expansion Tank Acceptance Volume fits
See also
Loop Water Expansion Volume: Both use system water volume.System Volume from Turnover Time: Both use system water volume.Boyle's Law: Both use fill pressure.Cavitation Number (Margin above Vapour Pressure): Both use fill pressure.Combined Gas Law: Both use fill pressure.Dalton's Law of Partial Pressures: Both use fill pressure.Loop hardware →
UniversityFluid Mechanics, HVAC & Refrigeration
Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning.
Expansion Tank Acceptance Volume explained
Water is nearly incompressible, so a closed loop with nowhere to expand will simply lift the relief valve: about 1 % of volume growth is enough to take a system from 12 psi to 100 psi. The expansion tank gives that growth somewhere to go by compressing a captive air cushion. The bladder-tank equation says the tank must be big enough that the expanded water squeezes the air from P₁ to P₂ without exceeding P₂: Vt = Vs·e ÷ (1 − P₁/P₂), where e is the net expansion factor, roughly 2.4 % for water heated from 45 °F fill to 200 °F operating.
The trap that ruins more tanks than any other is gauge versus absolute pressure. Boyle's law needs absolute, so add 14.7 psi (101 kPa) to both readings before entering them: a 12 psig fill is 26.7 psia and a 30 psig relief is 44.7 psia. Do it in gauge and you undersize the tank by roughly half. Worked example: 1,000 gal of system water, e = 2.4 %, 26.7/44.7 psia gives Vt = 24 ÷ 0.4027 ≈ 59.6 gal of tank, and you buy the next size up. Second trap: the tank's air pre-charge must be set to the fill pressure before the system is filled, with the tank isolated. A factory 12 psi pre-charge dropped into a 25 psi fill leaves you with a tank that is already full of water and a relief valve that weeps every afternoon.
Expansion Tank Acceptance Volume formula
- = Tank volume (L)
- = System water volume (L)
- = Net expansion factor (%)
- = Fill pressure (absolute) (kPa)
- = Maximum pressure (absolute) (kPa)
Cite this page
formula.expert. (2026, October 16). Expansion Tank Acceptance Volume Formula & Calculator. https://formula.expert/solvers/expansion-tank-sizing