System Volume from Turnover Time

V=R tV = R \, t
sig figs

Worked example: 1200 gpm with a 25 min turnover → 113,562 L (30,000 gal). Press Try an example to run it live, then adjust anything.

Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.

Where System Volume from Turnover Time fits

Your answer feeds
In this toolkit

See also

Cooling Tower Drift Loss: Both use recirculation rate.Cooling Tower Evaporation Rate: Both use recirculation rate.Cooling Tower Heat Rejection: Both use recirculation rate.Closed Loop Slug Dose Volume: Both use system volume.Dose Achieved from Chemical Added: Both use system volume.Glycol Dilution: Both use system volume.
3 more relatedHolding Time Index: Both use system volume.Expansion Tank Acceptance Volume: Both use system volume.Loop Water Expansion Volume: Both use system volume.
Here the solver did the work. Could you?

The holding time index →

UniversityProcess & Water Chemistry

Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning.

See your Report Card
Learning zone

System Volume from Turnover Time explained

VRt

Nine times out of ten the plant cannot tell you how much water is in the system, and the treatment program depends on knowing. If you have the pump curve or a flow meter, and you can time one complete circuit, the volume follows immediately: 1200 gpm circulating with a 25 minute turnover means 30,000 gallons in the loop. Timing the turnover is the practical trick: inject dye or a salt slug at the pump discharge and clock how long until it comes back around.

Design rules of thumb are worth carrying as a cross-check. Cooling towers are usually sized so the whole system turns over in about 10 minutes of recirculation, and hydronic heating loops in 15–20; if your measured turnover is far outside that, suspect the flow figure rather than the volume. And remember what "system volume" must include: sump, standpipes, riser, condenser bundles, and the full length of any buried run. Underestimating volume is the single most common reason a slug dose lands low.

System Volume from Turnover Time formula

V=R tV = R \, t
Where
  • VV= System volume (L)
  • RR= Recirculation rate (L/min)
  • tt= Turnover time (s)
Where this comes from

Worked from first principles: a definition, a balance or unit arithmetic, so it needs no outside source.

Revised 30 October 2026
Cite this page

formula.expert. (2026, October 30). System Volume from Turnover Time Formula & Calculator. https://formula.expert/solvers/system-volume-from-turnover