Maximum Power Transfer to a Matched Load
Also known as matched load · impedance matching · Jacobi's law · maximum power theorem · source matching
Worked example: 20 V behind 5 Ω → 20 W into a matched 5 Ω — press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Try different units for next level excitement!
Norton and the matched load →
UniversityCircuits & Electrical Power
Test your skills in the Exam Room: new numbers every attempt — free lessons for students, no sign-up, just pure learning. Find 1 more lesson on this formula.
share your results
Maximum Power Transfer to a Matched Load explained
Sweep a load resistance from zero to infinity across a source and the power it receives rises, peaks, and falls again. Too small and the voltage collapses; too large and the current does. The peak sits exactly where , and there the load takes . Twenty volts behind 5 Ω, matched by a 5 Ω load: the loop carries 2 A, and the load absorbs W.
Notice what else happened in that example — the source dissipated 20 W too. Matched transfer is 50% efficient, always, by construction. That is the classic misreading of this theorem: it maximises power delivered, not power saved. No utility matches its generators to the grid; a power system deliberately runs with source impedance far below load impedance so efficiency approaches 100% and voltage stays stiff. Matching belongs where the signal matters and the watts do not.
So it lives in RF and audio and instrumentation: antennas into 50 Ω feedlines, transmission lines terminated to stop reflections, a solar panel held at its maximum-power point by a tracking converter. And the AC version wants the load impedance to be the complex conjugate of the source, so a source that looks inductive must be met with capacitance — reactance cancelled first, resistance matched second.
Maximum Power Transfer to a Matched Load formula
- = Maximum load power (W)
- = Thevenin voltage (V)
- = Thevenin resistance (Ω)
Missing one of these? Work it out first, then come back
- Maximum load power — Power-Factor Correction kvar, Three-Phase Real Power
- Thevenin voltage — Norton Current from the Thevenin Equivalent, Thevenin Resistance from an Open-Circuit and Loaded Measurement
- Thevenin resistance — Thevenin Resistance from an Open-Circuit and Loaded Measurement, Norton Current from the Thevenin Equivalent