Three-Phase Real Power
Also known as 1.732 formula · three phase kW · √3 power formula
Worked example: 480 V, 100 A, 0.85 PF → 70.67 kW. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.
Where Three-Phase Real Power fits
- V_LWye Line and Phase Voltage
- I_LDelta Line and Phase Current
- PFPower Factor from Real and Apparent Power
- Three-phase power and power factor8 formulas
- Motor calculations5 formulas
See also
Single-Phase Real Power with Power Factor: Both use real power and line current.Three-Phase Motor Full-Load Current: Both use line-to-line voltage and power factor.Power Factor from Real and Apparent Power: Both use real power and power factor.Power-Factor Correction kvar: Both use real power and power factor.Delta Line and Phase Current: Both use line current.Voltage Drop, Three Phase: Both use line current.5 more related
Motor Locked-Rotor Starting Current: Both use line-to-line voltage.Three-Phase Apparent Power: Both use line-to-line voltage.Wye Line and Phase Voltage: Both use line-to-line voltage.Phase Angle from Power Factor: Both use power factor.Transformer Efficiency from Core and Copper Losses: Both use power factor.Three-phase power →
UniversityCircuits & Electrical Power
Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning. Find 2 more lessons on this formula.
Three-Phase Real Power explained
The √3 is the whole story of three-phase power. Each of the three phases carries Vphase × Iphase, but the meter and the nameplate quote line quantities, and the 120° spacing between phases turns the sum of three phase powers into √3 × VL × IL. Multiply by the power factor and you have the real, billable, heat-and-torque-producing watts. A 480 V feeder carrying 100 A at 0.85 PF delivers 1.732 × 480 × 100 × 0.85 ≈ 70.7 kW.
The trap is mixing line and phase values: the √3 belongs in the formula only when VL and IL are both line quantities. Drop the power factor and you get apparent power in VA, not watts: the two differ by 15% on that feeder, which is exactly why a 100 kVA transformer will not carry 100 kW of motor load. Nikola Tesla's polyphase patents of 1888 made this arithmetic the foundation of every industrial plant since.
Three-Phase Real Power formula
- = Real power (W)
- = Line-to-line voltage (V)
- = Line current (A)
- = Power factor
Three-phase power and power factor
8 formulasReal, reactive and apparent power, power factor, phase angle and correction kvar — the power triangle as an electrician uses it.
Motor calculations
5 formulasFull-load current, synchronous speed, slip, efficiency and input power — reading a motor nameplate and checking what it actually draws.
Cite this page
formula.expert. (2026, October 16). Three-Phase Real Power Formula & Calculator. https://formula.expert/solvers/three-phase-real-power