Three-Phase Real Power
Also known as 1.732 formula · three phase kW · √3 power formula
Worked example: 480 V, 100 A, 0.85 PF → 70.67 kW — press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Try different units for next level excitement!
Three-phase power →
UniversityCircuits & Electrical Power
Test your skills in the Exam Room: new numbers every attempt — free lessons for students, no sign-up, just pure learning. Find 2 more lessons on this formula.
share your results
Three-Phase Real Power explained
The √3 is the whole story of three-phase power. Each of the three phases carries Vphase × Iphase, but the meter and the nameplate quote line quantities, and the 120° spacing between phases turns the sum of three phase powers into √3 × VL × IL. Multiply by the power factor and you have the real, billable, heat-and-torque-producing watts. A 480 V feeder carrying 100 A at 0.85 PF delivers 1.732 × 480 × 100 × 0.85 ≈ 70.7 kW.
The trap is mixing line and phase values: the √3 belongs in the formula only when VL and IL are both line quantities. Drop the power factor and you get apparent power in VA, not watts — the two differ by 15% on that feeder, which is exactly why a 100 kVA transformer will not carry 100 kW of motor load. Nikola Tesla's polyphase patents of 1888 made this arithmetic the foundation of every industrial plant since.
Three-Phase Real Power formula
- = Real power (W)
- = Line-to-line voltage (V)
- = Line current (A)
- = Power factor
Missing one of these? Work it out first, then come back
- Real power — Single-Phase Real Power with Power Factor, Power Factor from Real and Apparent Power
- Line-to-line voltage — Single-Phase Real Power with Power Factor, Three-Phase Apparent Power
- Line current — Single-Phase Real Power with Power Factor, Three-Phase Apparent Power
- Power factor — Single-Phase Real Power with Power Factor, Power Factor from Real and Apparent Power
Three-phase power and power factor
8 formulasReal, reactive and apparent power, power factor, phase angle and correction kvar — the power triangle as an electrician uses it.
Motor calculations
5 formulasFull-load current, synchronous speed, slip, efficiency and input power — reading a motor nameplate and checking what it actually draws.