Motor Locked-Rotor Starting Current

Also known as locked rotor amps · LRA · motor inrush current · starting current · code letter kVA per horsepower · across the line starting current

ILR=1000 k P3 VI_{LR} = \frac{1000 \, k \, P}{\sqrt{3} \, V}
kVA/hp
sig figs

Worked example: 25 hp, 460 V, 6.3 kVA/hp → 197.7 A inrush. Press Try an example to run it live, then adjust anything.

Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.

Where Motor Locked-Rotor Starting Current fits

Missing an input?

See also

Three-Phase Motor Full-Load Current: The running current this inrush is a multiple of: usually six or seven times it.Percent Voltage Drop: Inrush is what causes the momentary sag that dims the lights; this turns the current into volts lost.Generator Sizing from Connected Load: Starting inrush, not running load, is what usually sizes a generator on a motor-heavy site.Three-Phase Apparent Power: Both use line-to-line voltage.Three-Phase Real Power: Both use line-to-line voltage.Wye Line and Phase Voltage: Both use line-to-line voltage.
Here the solver did the work. Could you?

Nameplate currents →

UniversityCircuits & Electrical Power

Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning.

See your Report Card
Learning zone

Motor Locked-Rotor Starting Current explained

ILRItMVP

At the instant of starting, an induction motor is a transformer with a shorted secondary. The rotor is not moving, no back-EMF opposes the supply, and the only thing limiting current is the winding impedance, so the motor pulls somewhere between five and eight times its full-load current until it accelerates. Manufacturers state this on the nameplate as a code letter, which stands for a range of locked-rotor kilovolt-amperes per horsepower. Look the letter's kVA/hp value up in your own code book, enter it here, and the arithmetic is straightforward: multiply by the horsepower to get locked-rotor kVA, then divide by √3 V to get amps. A 25 hp, 460 V motor at 6.3 kVA/hp draws about 198 A to start against roughly 30 A running.

What that inrush actually does is sag the voltage: momentarily, but sometimes visibly, and occasionally enough to drop out a contactor elsewhere on the panel or to stall the motor that caused it. The current is also strongly reactive at that instant, with a power factor down around 0.2, so it is nearly pure magnetizing current doing no work at all. This is the number that sizes soft starters, decides whether a wye-delta or autotransformer starter is worth the panel space, and, more than any running load, sizes a generator on a site with big motors.

Two cautions. The kVA/hp figure is a range per letter, and the code table gives a band, not a point: use the top of the band when the consequence of being wrong is a nuisance trip. And do not use this number for overload protection or conductor sizing: those follow the code's own tables and rules, which are built to let the inrush pass while still protecting the machine. Locked-rotor current tells you about the moment of starting; it says nothing about the hour that follows.

Motor Locked-Rotor Starting Current formula

ILR=1000 k P3 VI_{LR} = \frac{1000 \, k \, P}{\sqrt{3} \, V}
Where
  • ILRI_{LR}= Locked-rotor current (A)
  • kk= Locked-rotor kVA per horsepower (kVA/hp)
  • PP= Motor rating (hp)
  • VV= Line-to-line voltage (V)
Revised 31 October 2026
Cite this page

formula.expert. (2026, October 31). Motor Locked-Rotor Starting Current Formula & Calculator. https://formula.expert/solvers/motor-starting-current-locked-rotor