Pipe Internal Volume
Also known as gallons per foot of pipe · how much water is in a pipe
Enter your known values, leave one input blank, and solves for the missing one. Try different units for next level excitement!
Learning zone
Knowing the system volume is what turns a chemical dose rate into a number of litres to pour in. A 100 ft run of 4 in Schedule 40 steel holds π/4 × (4 in)² × 1200 in ≈ 15 080 in³ ≈ 65.3 US gallons, which is the origin of the plumber's constant "0.653 gallons per foot for 4-inch". Water treaters carry a whole table of these — 0.0408 gal/ft for ½ in, 0.163 for 1 in, 1.47 for 6 in — and estimate a building's loop volume by tallying pipe lengths from the riser diagram.
Use the true inside diameter, not the nominal size, or you will be out by 10–15% before you start: nominal 4 in Schedule 40 is 4.026 in ID, Schedule 80 is 3.826 in, and type L copper is 3.905 in. And remember the pipe is usually the small half of a system — an air handler coil, a buffer tank and a boiler can hold several times what the distribution piping does, which matters enormously when you are calculating how long a glycol charge or a biocide slug takes to circulate.
- = Internal volume
- = Inside diameter
- = Pipe length
- Internal volume — Air Changes per Hour (ACH), Expansion Tank Acceptance Volume
- Inside diameter — Hazen–Williams Head Loss, Equivalent Length of a Fitting
- Pipe length — Hazen–Williams Head Loss, Darcy–Weisbach Head Loss