Pipe Internal Volume
Also known as gallons per foot of pipe · how much water is in a pipe
Worked example: 1000 L held in 150 mm pipe → 56.588 m of run — press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Try different units for next level excitement!
What the pipe holds →
UniversityFluid Mechanics, HVAC & Refrigeration
Test your skills in the Exam Room: new numbers every attempt — free lessons for students, no sign-up, just pure learning.
share your results
Pipe Internal Volume explained
Knowing the system volume is what turns a chemical dose rate into a number of litres to pour in. A 100 ft run of 4 in Schedule 40 steel holds π/4 × (4 in)² × 1200 in ≈ 15 080 in³ ≈ 65.3 US gallons, which is the origin of the plumber's constant "0.653 gallons per foot for 4-inch". Water treaters carry a whole table of these — 0.0408 gal/ft for ½ in, 0.163 for 1 in, 1.47 for 6 in — and estimate a building's loop volume by tallying pipe lengths from the riser diagram.
Use the true inside diameter, not the nominal size, or you will be out by 10–15% before you start: nominal 4 in Schedule 40 is 4.026 in ID, Schedule 80 is 3.826 in, and type L copper is 3.905 in. And remember the pipe is usually the small half of a system — an air handler coil, a buffer tank and a boiler can hold several times what the distribution piping does, which matters enormously when you are calculating how long a glycol charge or a biocide slug takes to circulate.
Pipe Internal Volume formula
- = Internal volume (L)
- = Inside diameter (mm)
- = Pipe length (m)
Missing one of these? Work it out first, then come back
- Internal volume — Air Changes per Hour (ACH), Expansion Tank Acceptance Volume
- Inside diameter — Hazen–Williams Head Loss, Equivalent Length of a Fitting
- Pipe length — Hazen–Williams Head Loss, Darcy–Weisbach Head Loss