Ryznar Stability Index (RSI)
Also known as RSI
Worked example: pHs 7.31, pH 7.80 → RSI = 6.82. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value.
Where Ryznar Stability Index (RSI) fits
- pHsSaturation pH (pHs) for Langelier's Index · Saturation pH (pHs), Rigorous: from the Carbonate Equilibria
- pHpH from Hydrogen Ion Concentration · pH and pOH Relation
- Scaling and corrosion indices6 formulas
See also
Langelier Saturation Index (LSI): Both use saturation pH and measured pH.Puckorius (Practical) Scaling Index: Both use saturation pH.Saturation pH (pHs) for Langelier's Index: Both use saturation pH.Saturation pH (pHs), Rigorous: from the Carbonate Equilibria: Both use saturation pH.Cooling Tower LSI at Cycles of Concentration: Both use measured pH.Langelier Saturation Index from a Full Water Analysis: Both use measured pH.Ryznar and Puckorius →
UniversityProcess & Water Chemistry
Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning. Find 1 more lesson on this formula.
Ryznar Stability Index (RSI) explained
John Ryznar worked at Nalco in 1944 and noticed that Langelier's index told you the direction of a water's tendency but not how hard it would push. He rebuilt it as an empirical scale calibrated against real municipal distribution data: RSI = 2· − pH, always positive, running roughly from 4 to 10. Below about 6 the water lays down scale; 6 to 7 is the sweet spot most cooling and distribution systems aim for; above 7 the water is increasingly aggressive and above 8.5 it is downright corrosive. A tower at pH 7.8 with 7.31 gives RSI = 14.62 − 7.8 = 6.82: mildly aggressive, contradicting the +0.49 LSI that called the same water scaling.
That contradiction is the point, not a bug. LSI says the water can deposit calcium carbonate; RSI says there is not enough driving force to build a protective film fast enough to matter. Field practice is to run both and treat a water only when they agree, or to lean on RSI in distribution mains and on LSI in heated equipment where the skin temperature does the deciding. The one thing you should never do is compute RSI from a you looked up at 25 °C and a pH you measured on hot water: both numbers have to describe the same fluid at the same temperature.
Ryznar Stability Index (RSI) formula
- = Ryznar Stability Index
- = Saturation pH
- = Measured pH
- Ryznar, J. W. (1944). A new index for determining amount of calcium carbonate scale formed by a water. Journal AWWA, 36. Read it