Available Short-Circuit Current from Percent Impedance
Also known as available fault current · AIC rating · bolted fault current · infinite bus method · transformer let-through current
Worked example: 601.4 A FLA at 5% Z → 12 028 A available. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.
Where Available Short-Circuit Current from Percent Impedance fits
See also
Three-Phase Apparent Power: Supplies the full-load current this calculation starts from.Per-Unit Base Impedance: The same relation written in per unit: I_SC in pu is simply 1/Z_pu.Transformer Percent-Impedance Voltage Drop: Both use percent impedance.Three-Phase Motor Full-Load Current: Both use full-load current.Transformer Full-Load Current: Both use full-load current.Sag and fault →
UniversityCircuits & Electrical Power
Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning.
Available Short-Circuit Current from Percent Impedance explained
Percent impedance is a strange-looking number until you know its definition: it is the percentage of rated voltage that must be applied to a transformer with its secondary shorted to drive exactly full-load current. Turn that around and it tells you the fault current straight away. If 5% of the volts pushes full-load amps through the short, then 100% of the volts pushes twenty times that. A 500 kVA, 480 V unit with 601 A full load and 5% impedance can deliver A into a bolted fault.
That number is not academic. It sets the interrupting rating of every breaker and fuse downstream, and equipment applied above its rating does not merely trip late: it can fail explosively, which is the scenario arc-flash studies exist to prevent. It is also why "buy the transformer with the lowest impedance" is bad advice: a lower %Z gives better voltage regulation and worse fault duty, and the sweet spot is a design decision, not a default.
The assumption hiding in this calculation is an infinite primary source, so it deliberately overestimates. Real utility supplies have their own impedance, and the cable between the transformer and the fault adds more, so the true available current at a panel forty metres away is lower: sometimes much lower. Overestimating is the safe direction for equipment ratings but the unsafe direction for coordination studies, where a fault current that turns out too small may fail to clear a fuse in time.
Available Short-Circuit Current from Percent Impedance formula
- = Available short-circuit current (A)
- = Full-load current (A)
- = Percent impedance (%)
Cite this page
formula.expert. (2026, October 16). Available Short-Circuit Current from Percent Impedance Calculator. https://formula.expert/solvers/short-circuit-current-percent-impedance