Transformer Percent-Impedance Voltage Drop
Also known as impedance drop · transformer voltage drop · IZ drop · load droop · percent impedance drop
Worked example: 1000 kVA, 480 V, 5.75% Z at full load → 27.6 V. Press Try an example to run it live, then adjust anything.
Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.
Where Transformer Percent-Impedance Voltage Drop fits
See also
Voltage Regulation: The measured version of the same droop, stated as a percentage of the loaded voltage.Available Short-Circuit Current from Percent Impedance: The other use of the same nameplate number, at the opposite extreme of loading.Power Factor from Real and Apparent Power: Both use actual load.Reactive Power (Power Triangle): Both use actual load.Three-Phase Apparent Power: Both use actual load.Transformer Full-Load Current: Both use actual load.Sag and fault →
UniversityCircuits & Electrical Power
Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning.
Transformer Percent-Impedance Voltage Drop explained
The same percent impedance that sets fault current also sets the voltage a transformer loses inside itself. By definition, at full load the internal drop is exactly %Z of rated volts, and the drop scales with loading. So a 1000 kVA, 480 V transformer with 5.75% impedance loses V of its own winding at nameplate load, and 13.8 V at half load. That is why the secondary of a heavily loaded transformer sits low and the tap changer exists.
Treat this as an upper bound rather than a prediction, because it adds the resistive and reactive drops arithmetically when they are really at right angles to each other and to the load current. The true drop depends on power factor: at unity PF a mostly reactive impedance costs far less than this suggests, while at 0.8 lagging the resistive and reactive parts line up closer with the load and the answer here is close to right. The exact form is .
The counter-intuitive part is that a leading power factor can make the drop go the other way: a lightly loaded feeder with capacitor banks still switched in can push the secondary above nominal, which is a real problem on rural circuits and on distribution feeders with a lot of solar. High impedance is not simply a defect either: utilities sometimes specify a higher %Z deliberately to hold fault current down to what the existing switchgear can interrupt, and accept the poorer regulation as the price.
Transformer Percent-Impedance Voltage Drop formula
- = Impedance voltage drop (V)
- = Percent impedance (%)
- = Actual load (kVA) (W)
- = Transformer rating (kVA) (W)
- = Rated secondary voltage (V)
Cite this page
formula.expert. (2026, October 16). Transformer Percent-Impedance Voltage Drop Calculator. https://formula.expert/solvers/transformer-impedance-voltage-drop