Electrical Resistivity of Aluminium at 20 °C

ρAl=2.65×10−8 Ω⋅m\rho_{\mathrm{Al}} = 2.65 \times 10^{-8}\ \Omega{\cdot}\text{m}
Value2.65e-8 Ω·m
StatusMeasured: ± 5.00e-11 Ω·m (0.0019 relative)
SourceIEC 60028 / NFPA 70 (National Electrical Code) Ch. 9
CategoriesMaterial PropertiesEngineering & Trade
Electrical Resistivity of Aluminium at 20 °C in every electrical resistivity unit
nanoohm meter26.5 nΩ·m
ohm circular mil per foot15.940558 Ω·cmil/ft
microohm centimeter2.65 μΩ·cm
microohm meter0.0265 μΩ·m
ohm square millimeter per meter0.0265 Ω·mm²/m
milliohm centimeter0.00265 mΩ·cm
ohm centimeter0.00000265 Ω·cm
ohm meter2.6500000e-08 Ω·m
kiloohm centimeter2.6500000e-09 kΩ·cm
megaohm centimeter2.6500000e-12 MΩ·cm

Learning zone

Aluminium conducts about 61 % as well as copper by volume but is only 30 % as dense, so per kilogram it is roughly twice as good a conductor — the reason every overhead transmission line and most large service entrances are aluminium. Sizing rule of thumb: to match a copper conductor's ampacity you go up about two AWG sizes. The trade constant for voltage drop is K = 21.2 Ω·cmil/ft against copper's 12.9.

The failure mode is the connection, not the conductor. Aluminium forms a tough insulating oxide the instant it is exposed, it creeps under the sustained pressure of a screw terminal, and its expansion coefficient differs from that of the brass or copper hardware clamping it. Cycle that joint and contact pressure decays, resistance climbs and the terminal overheats — the mechanism behind the 1960s-70s aluminium branch-circuit fires and the reason for AL/CU-rated devices, antioxidant compound, correct torque and periodic retorque. The wire is fine; the interface is what needs engineering.