Electrical Resistivity of Aluminium at 20 °C
| Value | 2.65e-8 Ω·m |
| Status | Measured: ± 5.00e-11 Ω·m (0.0019 relative) |
| Source | IEC 60028 / NFPA 70 (National Electrical Code) Ch. 9 |
| Categories | Material PropertiesEngineering & Tradeelectrical-trade |
| ohm meter | 2.6500000e-08 Ω·m |
| ohm centimeter | 0.00000265 Ω·cm |
| microohm centimeter | 2.65 μΩ·cm |
| nanoohm meter | 26.5 nΩ·m |
Learning zone
Aluminium conducts about 61 % as well as copper by volume but is only 30 % as dense, so per kilogram it is roughly twice as good a conductor — the reason every overhead transmission line and most large service entrances are aluminium. Sizing rule of thumb: to match a copper conductor's ampacity you go up about two AWG sizes. The trade constant for voltage drop is K = 21.2 Ω·cmil/ft against copper's 12.9.
The failure mode is the connection, not the conductor. Aluminium forms a tough insulating oxide the instant it is exposed, it creeps under the sustained pressure of a screw terminal, and its expansion coefficient differs from that of the brass or copper hardware clamping it. Cycle that joint and contact pressure decays, resistance climbs and the terminal overheats — the mechanism behind the 1960s-70s aluminium branch-circuit fires and the reason for AL/CU-rated devices, antioxidant compound, correct torque and periodic retorque. The wire is fine; the interface is what needs engineering.