Sensible Heat Ratio (SHR)
Also known as SHR
Enter your known values, leave one input blank, and solves for the missing one. Try different units for next level excitement!
Learning zone
Every cooling coil does two jobs at once — dropping temperature and wringing out water — and SHR says how the work splits. A dry Denver office runs SHR 0.90; a Houston restaurant with a hundred breathing customers and a dish line might sit at 0.65; a natatorium is lower still. Equipment has its own SHR, set by coil rows, fin spacing and face velocity, and the design rule is simple: the coil's SHR must be at or below the room's, or moisture accumulates.
This is where oversizing does its damage. A unit with more capacity than the room needs satisfies the thermostat quickly, runs short cycles, and never lets condensate form — so it delivers a high effective SHR regardless of nameplate, and the building runs 74 °F at 65 % RH with mould in the closets. Slowing the fan lowers coil SHR (colder, wetter coil); speeding it raises SHR. Worked example: 24,000 BTU/hr sensible plus 6,000 latent gives SHR = 24,000/30,000 = 0.80, the textbook residential default. Given SHR and one component you can recover the other: 30 kW sensible at SHR 0.75 implies 10 kW of latent load and a 40 kW coil.
- = Sensible heat ratio
- = Sensible load
- = Latent load
- Sensible heat ratio — Energy Efficiency Ratio (EER), EER to COP Conversion
- Sensible load — Air Sensible Heat (1.08 Rule), Chiller Heat Rejection
- Latent load — Air Latent Heat (0.68 Rule), Chiller Heat Rejection