Orifice Plate Flow

Also known as orifice meter · differential pressure flow meter · beta ratio · square edged orifice · iso 5167

Q=Cd1−β4⋅πd242 ΔPρQ = \frac{C_d}{\sqrt{1 - \beta^{4}}}\cdot\frac{\pi d^{2}}{4}\sqrt{\frac{2\,\Delta P}{\rho}}

or type the values yourself

sig figs

Worked example: 50 mm bore in 100 mm pipe, 20 kPa across it → 469.4 L/min of water. Press Try an example to run it live, then adjust anything.

Enter your known values, leave one input blank, and solves for the missing one. Tap a variable’s symbol to see what it means, with a typical value. Change any unit and the answer follows.

Where Orifice Plate Flow fits

Missing an input?

See also

Venturi Meter Flow: the same equation with a far better discharge coefficient and far less permanent lossBernoulli's Equation (Two Points): where the square root of the pressure drop comes from
Here the solver did the work. Could you?

Metering the flow →

UniversityFluid Mechanics, HVAC & Refrigeration

Test your skills in the Exam Room: new numbers every attempt. Free lessons for students, no sign-up, just pure learning.

See your Report Card
Learning zone

Orifice Plate Flow explained

dDρΔPCdQ

An orifice plate is a disc with a hole, bolted between flanges, and it has survived a century of better ideas because it is cheap, has no moving parts, and is described by an international standard anyone can audit. Drop the flow through a restriction and the pressure falls by an amount proportional to the square of velocity, so the flow comes back out as a square root. A 50 mm bore in a 100 mm line with 20 kPa across it passes about 469 L/min of water. Double the flow and you need four times the differential, which is exactly why an orifice meter's usable turndown is only about 3 or 4 to 1: at a third of full flow the differential has fallen to a ninth and the transmitter is reading noise.

The discharge coefficient near 0.61 is not a fudge factor, it is the vena contracta. The jet keeps converging for a diameter or so downstream of the plate, so the true minimum flow area is smaller than the drilled hole. ISO 5167 gives the Reader-Harris/Gallagher equation for CdC_d as a function of β\beta and Reynolds number, and it stays within a few tenths of a percent when the installation follows the standard. The velocity-of-approach factor 1/1−β41/\sqrt{1-\beta^4} is a separate correction, accounting for the fact that the upstream fluid was already moving.

What surprises people is how much of the accuracy lives in the pipe rather than the plate. The standard demands long straight runs, typically 10 to 40 diameters upstream depending on what disturbance sits there, because a swirl left over from two out-of-plane elbows will bias the reading by several percent and no calibration will find it. The other quiet killer is a nicked or rounded upstream edge: an orifice plate installed backwards, or one that has been in erosive service for a few years, reads high by a margin that nothing on the transmitter reveals.

Orifice Plate Flow formula

Q=Cd1−β4⋅πd242 ΔPρQ = \frac{C_d}{\sqrt{1 - \beta^{4}}}\cdot\frac{\pi d^{2}}{4}\sqrt{\frac{2\,\Delta P}{\rho}}
Where
  • QQ= Volumetric flow (L/min)
  • CdC_d= Discharge coefficient
  • dd= Orifice bore (mm)
  • DD= Pipe inside diameter (mm)
  • ΔP\Delta P= Differential pressure (kPa)
  • ρ\rho= Fluid density (kg/m³)
Revised 31 October 2026
Cite this page

formula.expert. (2026, October 31). Orifice Plate Flow Formula & Calculator. https://formula.expert/solvers/orifice-plate-flow