Nominal mains voltage (North America)
| Value | 120 V |
| Status | Typical value: varies by about ± 6 V in practice |
| Source | ANSI C84.1: nominal system voltage, Range A tolerance |
| Categories | ElectromagneticEngineering & Trade |
| Unit | Value |
|---|---|
| volt | 120 V |
| millivolt | 120,000 mV |
| kilovolt | 0.12 kV |
| picovolt | 120,000,000,000,000 pV |
| nanovolt | 120,000,000,000 nV |
| microvolt | 120,000,000 μV |
| megavolt | 0.00012 MV |
| gigavolt | 1.2000000e-07 GV |
Learning zone
Edison's original DC distribution ran at 110 V because that was what his carbon-filament lamps liked, and the number survived the switch to alternating current by inertia. It drifted upward over the decades (110, then 115, then 117) as utilities raised voltage to squeeze more power through existing copper, and settled at a nominal 120 V. Residential service arrives as 240 V centre-tapped, giving two 120 V legs for lighting and receptacles and the full 240 V for ranges, dryers and air conditioning.
ANSI C84.1 defines the tolerance rather than a single number: Range A is 114 to 126 V at the utilisation point, so any calculation that treats 120 V as exact is already working to about ±5%. That band is why the National Electrical Code caps branch-circuit voltage drop at 3% and total feeder-plus-branch drop at 5%, and why motors carry a nameplate utilisation voltage of 115 V rather than 120.