Practice problems
Answer key at the back. Work in the units each problem states.
DC Circuit Foundations
1. Ohm's Law — A 40 Ω resistor is connected straight across a 200 V bench supply. Determine the current the resistor draws.
2. Ohm's Law — A shunt element on a DC test rig drops 250 V while carrying 5 A. Determine the resistance of the element.
3. Charge in motion — A plating cell is run at a steady 8 A for 210 s. Calculate the charge passed through the cell.
4. Charge in motion — A lithium cell for a portable instrument is rated 2000 mA·h. Delivered in full, that rating is a quantity of charge. Determine the charge the cell can deliver, in coulombs.
5. Power, three ways — A DC drive on a conveyor is measured at 120 V across its terminals while it draws 2 A. No resistance is quoted anywhere on the sheet. Calculate the power the drive is taking from the supply.
6. Power, three ways — A 20 Ω braking resistor carries 2 A during a stop. Nobody has metered the voltage across it. Calculate the power the resistor turns into heat.
7. Series and parallel — On a breadboard, a 15 Ω resistor and a 60 Ω resistor are wired end to end, so the same current must pass through both in turn. Calculate the resistance the pair presents between the outer ends.
8. Series and parallel — On the same breadboard, a 40 Ω resistor and a 60 Ω resistor are wired side by side between one pair of nodes, so the current arriving has two paths open to it. Calculate the resistance the pair presents between those two nodes.
9. Dividers — A sensor input is fed from a 15 V rail through a two-resistor chain: 10 kΩ from the rail down to the tap, then 5 kΩ from the tap down to ground. The input itself draws no appreciable current. Calculate the voltage at the tap, measured to ground.
10. Dividers — A 6 A supply current arrives at a node and splits between two parallel branches: branch 1 is 4 Ω, branch 2 is 2 Ω. Determine the current flowing in branch 1.
11. The real wire — A 300 m run of copper cable has a conductor cross-section of 4 mm². Copper's resistivity is 1.68 × 10⁻⁸ Ω·m at working temperature. Calculate the DC resistance of that one conductor.
12. The real wire — A copper field winding measures 25 Ω cold, on the bench at 20 °C. In service it settles at 55 °C. Copper's temperature coefficient is α = 0.00393 per K, referred to 20 °C. Determine the winding's resistance at its working temperature.
13. The Breadboard Final — Last board of the lab. A 20 V bench supply feeds a 2 Ω resistor, and beyond it a 6 Ω and a 3 Ω resistor sit side by side across the remaining pair of nodes. The 2 Ω part in your hand is marked 100 W. Work each line — every answer feeds the next. Determine whether the 2 Ω resistor's wattage rating is adequate, one line at a time.
14. The Breadboard Final — Bonus mark, before the bench is cleared: the supply's own 4 Ω dropping resistor is carrying 5 A. Determine the power that resistor is dissipating.
Kirchhoff & the Network Theorems
15. The loop rule — A single loop on the bench: one supply feeding three elements in series. The meter reads 7 V across the first element, 8 V across the second and 9 V across the third. Determine the source voltage driving the loop.
16. The loop rule — A single loop on the bench: one supply feeding three elements in series. The meter reads 15 V across the first element, 20 V across the second and 25 V across the third. Determine the source voltage driving the loop.
17. The node rule — A distribution block in a panel is fed by one incoming conductor and split into three outgoing circuits. A clamp meter on the three outgoing legs reads 7 A, 10 A and 13 A. Determine the current in the incoming conductor.
18. The node rule — A junction box takes 12 A on its feed and splits it three ways. Two of the outgoing legs clamp at 3 A and 4 A. The third runs into a wall and cannot be clamped. Determine the current in the third leg.
19. Two laws together — The same 20 V divider is being checked at the bench. The technician's probe reaches the tap and reads 5 V there, but the upper resistor's body is under a heatsink and cannot be probed across. Determine the drop across the upper resistor.
20. Two laws together — The same 24 V divider is being checked at the bench. The technician's probe reaches the tap and reads 6 V there, but the upper resistor's body is under a heatsink and cannot be probed across. Determine the drop across the upper resistor.
21. Thevenin from two readings — A different module from the same batch is already characterised: 12 V open circuit, with 10 Ω of internal resistance. A 30 Ω load is about to be clipped across its terminals. Determine what the meter will read at the terminals once that load is connected.
22. Thevenin from two readings — A different module from the same batch is already characterised: 15 V open circuit, with 10 Ω of internal resistance. A 40 Ω load is about to be clipped across its terminals. Determine what the meter will read at the terminals once that load is connected.
23. Norton and the matched load — A bench source has been reduced to its Thevenin equivalent: 24 V behind 8 Ω. The lab wants the same source written the other way round, as a current source with the resistance in parallel. Determine the Norton current of the equivalent.
24. Norton and the matched load — A transducer's output stage is modelled as 12 V behind 2 Ω. The design team wants to know the very best a load could ever do on this output, before they choose one. Determine the greatest power any load can draw from this source.
25. Delta to wye and back — A resistance bridge refuses to reduce: no two resistors in it are cleanly in series or in parallel. One triangle of the network runs 6 Ω between nodes A and B, 12 Ω between B and C, and 18 Ω between C and A. The plan is to redraw that triangle as a star. Determine the star arm that meets node A.
26. Delta to wye and back — A three-terminal network is drawn as a star: 4 Ω from node A to the centre, 8 Ω from node B, and 16 Ω from node C. To merge it with a delta-connected bank next to it, the star has to be redrawn as a triangle. Determine the triangle leg that spans nodes A and B.
27. Design the drop — A status LED is to run from a 5 V rail. Its datasheet gives a forward voltage of 1.8 V at the design current of 20 mA, and the LED will be fed through a single series resistor. Determine the series resistance the design calls for, then choose the part to fit.
28. Design the drop — An indicator LED is to run from a 24 V rail. Its datasheet gives a forward voltage of 2 V at the design current of 20 mA, and the LED will be fed through a single series resistor. Determine the series resistance the design calls for, then choose the part to fit.
29. The Black Box Final — Last box of the day. A sealed module comes back from the field with no data on it. Two readings go in the log: 12 V across its terminals with nothing connected, and 8 V with a 10 Ω test load clipped on. The bench has a matched load resistor rated 25 W, and the question is whether it can be left running. (No calculator — the numbers are chosen to fit in your head.) Work each line; every answer feeds the next. Determine whether that resistor is safe as the matched load, one line at a time.
30. The Black Box Final — Bonus mark, on the way out: the same module measures 20 Ω of Thevenin resistance, and the drawer holds resistors of every value. A junior asks which one to clip on for the most power in the load. Determine the load resistance that draws the most power.
Storage & AC Impedance
31. Capacitance — A 10 µF snubber capacitor is found holding 1 mC of charge after the drive is de-energised. Determine the voltage still standing across its terminals.
32. Capacitance — A 220 µF capacitor bank is charged to 100 V and then isolated for a hipot check. Calculate the energy stored in the bank.
33. Capacitor combinations — Two capacitors, 80 µF and 20 µF, are wired in SERIES across a control-panel bus. Calculate the total capacitance the bus sees.
34. Capacitor combinations — Two capacitors, 6 µF and 12 µF, are wired in PARALLEL across the same DC link. Calculate the total capacitance across the link.
35. RC transients — A 100 µF capacitor is bled to ground through a 22 kΩ discharge resistor when the cabinet door opens. Calculate the time constant of that discharge path.
36. RC transients — A safety standard requires a 200 µF DC-link capacitor to reach a safe voltage on a 3 s time constant. Determine the bleed resistance that gives that time constant.
37. Inductors — A contactor coil of 400 mH sits in a circuit whose total resistance is 200 Ω. Calculate the time constant of the coil circuit.
38. Inductors — A relay circuit of 50 Ω is measured to settle on a 5 ms time constant. Determine the inductance of the relay coil.
39. RMS and peak — A true-RMS meter across a 208 V branch circuit reads 208 V with the load running. Determine the peak voltage of that sine wave.
40. RMS and peak — An oscilloscope on a supply feeder shows a clean sine cresting at 170 V above zero. Determine the RMS voltage a panel meter would report on that same feeder.
41. Reactance — A 250 mH line reactor is fed from a 60 Hz supply. Calculate the inductive reactance the reactor presents at that frequency.
42. Reactance — A 10 µF power-factor capacitor is connected to a 50 Hz supply. Calculate the capacitive reactance it presents at that frequency.
43. Impedance — A single-phase load is measured as 30 Ω of resistance in series with 40 Ω of reactance. Calculate the impedance magnitude of the load.
44. Impedance — A coil measures 45 Ω on a DC resistance bridge, and its impedance at line frequency is 75 Ω. Determine the reactance of the coil at that frequency.
45. Resonance — A tuned trap for a harmonic filter is built from a 250 mH coil and a 100 nF capacitor in series. Calculate the frequency at which that trap resonates.
46. Resonance — A trap must resonate at 2000 Hz, and the only capacitor in the stores is 100 nF. Determine the inductance the coil must have.
47. Filters and decibels — A first-order low-pass filter on a sensor input uses a 10 kΩ resistor feeding a 1 nF capacitor to ground. Calculate the −3 dB corner frequency of that filter.
48. Filters and decibels — A line filter puts a 50 mH choke in series with a 100 Ω load. Calculate the −3 dB corner frequency of that filter.
49. The Resonance Bench — Last bench of the term. A tuned tank is built from a 4 mH coil and a 10 µF capacitor, and the sheet gives its loaded quality factor as 4. The channel it must sit in is specified at no more than 400 Hz wide. No calculator: today take 1/(2π) as 0.16, so 2π is 6.25, and every line lands whole. Work each line — every answer feeds the next. Determine whether this tank fits inside the specified channel, one line at a time.
50. The Resonance Bench — Bonus mark, on the way out: a second tank centres on 160 Hz, and the specification calls for a passband exactly 20 Hz wide. Determine the quality factor that tank must have.
AC Power & the Bill
51. Power factor — A wattmeter on a single-phase compressor reads 9972 W. The panel meters beside it show 277 V and 45 A. Determine the power factor of the compressor.
52. Power factor — A wattmeter on a single-phase compressor reads 2496 W. The panel meters beside it show 208 V and 15 A. Determine the power factor of the compressor.
53. The power triangle — A plant's monthly bill quotes an average power factor of 0.95 lagging. Determine the phase angle between the supply voltage and the current.
54. The power triangle — A plant feeder is supplying 39 kVA to a bank of motors, and the wattmeter on the same feeder reads 36 kW. Calculate the reactive power the feeder is carrying.
55. Three-phase power — A three-phase panel on a 480 V system is measured at 40 A per line. Determine the apparent power the panel is drawing.
56. Three-phase power — A 75 kW three-phase load runs from a 600 V system at a power factor of 0.85. Determine the current in each line conductor.
57. Wye and delta systems — A delta-connected heater bank is built from three elements, and a clamp meter around one element inside the delta reads 60 A. Determine the current in each line conductor feeding the bank.
58. Wye and delta systems — A delta-connected heater bank is built from three elements, and a clamp meter around one element inside the delta reads 15 A. Determine the current in each line conductor feeding the bank.
59. Power-factor correction — A plant draws 150 kW at a power factor of 0.75 lagging. The utility's tariff penalises anything below 0.9, so the plant engineer proposes a capacitor bank. Calculate the capacitor rating needed to lift the power factor to 0.9.
60. Power-factor correction — A 13.3 kvar capacitor bank was installed on one feeder, and it moved that feeder's power factor from 0.8 to 0.9 exactly. Determine the real power the feeder is carrying.
61. The meter — A 25 kW compressor runs for 100 hours in a month, on a tariff of $0.10 per kilowatt-hour. Determine what that compressor adds to the month's electricity bill.
62. The meter — A 25 kW circulating pump runs continuously for 100 hours in a billing period. Calculate the energy the pump consumes over that period.
63. Feeders and voltage drop — A single-phase load draws 25 A down a 60 m run of 6 mm² copper. Take the resistivity of copper as 0.0172 Ω·mm²/m. Calculate the voltage lost in the run.
64. Feeders and voltage drop — A balanced three-phase feeder carries 25 A per line down a 100 m run of 10 mm² copper. Take the resistivity of copper as 0.0172 Ω·mm²/m. Calculate the line-to-line voltage lost in the run.
65. Battery runtime — A 200 Ah battery bank is to supply a steady 80 A. Treat the pack as ideal for this first estimate — the amp-hour figure taken at face value. Calculate the runtime the nameplate promises.
66. Battery runtime — A 100 Ah lead-acid bank is rated at the 20-hour discharge rate and has a Peukert exponent of 1.2. It is asked to hold a steady 20 A. Determine the runtime the pack will actually deliver.
67. The Utility Audit — The plant's main motor feeder is metered at 400 V, 125 A per line, power factor 0.80 lagging. The motor runs 200 hours in the billing month, energy is charged at 10 ¢/kWh, and the utility's demand tariff rewards a unity power factor. Today √3 = 1.73. Determine the capacitor bank, in kvar, that would take this feeder to unity — working from the metered load to the invoice on the way.
68. The Utility Audit — Bonus mark, on the way out: maintenance leaves a 15 kW process heater running for 50 hours of the same month, on the same 10 ¢/kWh tariff. Determine what that heater adds to the bill.
Motors, Transformers & Generators
69. Synchronous speed and slip — A 4-pole motor on a 50 Hz supply drives a conveyor. A stroboscope on the shaft reads 1470 rpm at full load. Determine the percent slip at that load.
70. Synchronous speed and slip — A nameplate on a 60 Hz machine gives its synchronous speed as 900 rpm. The winding data plate has gone missing. Determine how many poles the stator is wound for.
71. Torque from power — A torque transducer on a test bed reads 79.6 N·m while the shaft holds a steady 900 rpm. Determine the mechanical power the shaft is transmitting.
72. Torque from power — A 7.5 kW motor drives a centrifugal pump through a rigid coupling. Its nameplate speed at that output is 900 rpm. Calculate the torque the shaft delivers at rated output.
73. Motor efficiency — A test cell runs a motor at rated load. A power analyser on the supply reads 20 kW going in, and a dynamometer measures 17 kW coming off the shaft. Determine the motor's efficiency.
74. Motor efficiency — A ventilation fan's motor is metered at 50 kW input while running. Its nameplate quotes an efficiency of 85%. Calculate the mechanical power reaching the fan shaft.
75. Nameplate currents — A 11 kW three-phase motor is fed at 400 V. Its nameplate gives a power factor of 0.85, an efficiency of 88%, and a locked-rotor current 6 times full load. Determine the motor's full-load current, then the inrush it draws at the instant of an across-the-line start.
76. Nameplate currents — A 15 kW three-phase motor is fed at 400 V. Its nameplate gives a power factor of 0.9, an efficiency of 88%, and a locked-rotor current 6.5 times full load. Determine the motor's full-load current, then the inrush it draws at the instant of an across-the-line start.
77. Transformers — A dry-type transformer is wound with 500 turns on the primary and 100 turns on the secondary. The primary is energised at 600 V. Calculate the secondary voltage at no load.
78. Transformers — A rewind shop must produce 300 V from a 600 V supply. The primary coil is already wound with 300 turns. Determine how many turns the secondary needs.
79. Sag and fault — A technician meters a transformer secondary twice: 420 V with the load switched off, and 400 V with the plant running at rated load. Determine the transformer's percent voltage regulation.
80. Sag and fault — A 500 kVA transformer with a nameplate impedance of 5% supplies a rated secondary of 600 V. The connected load sits at 375 kVA. Calculate the volts lost inside the transformer's own windings at that loading.
81. Generator sizing — A water-treatment plant schedules 500 kW of connected load onto its standby system. The consultant's demand factor for that schedule is 0.6, and the client wants 10% spare capacity for growth. Calculate the continuous rating the standby set must have.
82. Generator sizing — A clamp meter on the main feeder of a pump house reads 150 A per line at 400 V, with the plant's power factor logged at 0.9. Determine the real power the pump house is drawing.
83. The Machine Room Final — Last machine of the commissioning day. A 6-pole induction motor runs on a 50 Hz supply at 400 V, three phase. A strobe reads 960 rpm at full load, a dynamometer measures 81 kW at the shaft, and the nameplate gives η = 90% and PF = 0.866. Work each line — every answer feeds the next. Read the motor end to end: field speed, slip, input power, line current.
84. The Machine Room Final — Bonus mark, on the way out: the same starter panel holds a motor drawing 60 A at full load, and its nameplate quotes a locked-rotor current 6 times that. Determine the inrush the starter contacts see at the instant of an across-the-line start.
Electromagnetics Basics
85. Coulomb's Law — Two conducting spheres on an electrostatics test jig hold 10 µC and 4 µC, their centres 0.2 m apart. (kₑ = 9.00 × 10⁹ N·m²/C²) Calculate the electrostatic force between the spheres.
86. Coulomb's Law — In a powder-coating booth, a charged particle carrying 10 µC drifts 0.2 m from a grounded electrode holding 4 µC. (kₑ = 9.00 × 10⁹ N·m²/C²) Determine the electrostatic force acting between the two charges.
87. A charge in a magnetic field — A charge of 80 µC crosses a magnet's gap at 250 m/s, square across the field lines, and a force of 8 mN is measured on it. Determine the flux density of the field in the gap.
88. A charge in a magnetic field — A charge of 75 µC crosses a magnet's gap at 400 m/s, square across the field lines, and a force of 15 mN is measured on it. Determine the flux density of the field in the gap.
89. Wires and forces — A 0.5 m length of armature conductor sits in the 0.25 T gap of a machine's field magnet, lying square across the field, carrying 16 A. Calculate the force the field exerts on that length of conductor.
90. Wires and forces — Two busbars in a switchboard run parallel for 5 m, 0.25 m apart, carrying 200 A and 200 A in the same direction. (µ₀ = 4π × 10⁻⁷ T·m/A) Calculate the magnitude of the force each busbar exerts on the other.
91. The solenoid — A relay's operating coil is wound with 2000 turns over a length of 0.5 m and carries 3 A. (µ₀ = 4π × 10⁻⁷ T·m/A) Calculate the magnetic field inside the coil.
92. The solenoid — A 0.25 m solenoid on a test bench carries 500 turns of magnet wire and is driven at 6 A. (µ₀ = 4π × 10⁻⁷ T·m/A) Calculate the magnetic field inside the coil.
93. Flux and Faraday — A search coil of a single turn encloses 0.025 m² and is held in a uniform 1.2 T field, tilted so that its normal makes 60° with the field lines. Calculate the magnetic flux threading the loop.
94. Flux and Faraday — A 150-turn search coil sits in a magnet's gap. When the magnet is de-energised, the flux through the coil falls by 10 mWb over 0.25 s. Determine the EMF induced in the coil while the flux is falling.
95. Motional EMF — A 1.5 m bar slides on rails square across a 0.4 T field, and a meter across the rails reads 12 V. Determine the speed of the bar.
96. Motional EMF — A 1.5 m bar slides on rails square across a 0.4 T field, and a meter across the rails reads 12 V. Determine the speed of the bar.
97. The Induction Gauntlet — Last bench of the term. A solenoid 0.5 m long carries 2000 turns at 10 A. A search coil of 10 turns and 100 cm² sits inside it, face-on to the field. Two ways to get a voltage out of this rig are on the table: kill the solenoid's current and let the flux through the search coil collapse to nothing in 50 ms, or slide a 1.2 m bar along rails at 20 m/s through the same field. (No calculator. Today µ₀ = 1.25 × 10⁻⁶ T·m/A.) Work each line — every answer feeds the next. Determine which of the two methods delivers the larger EMF, one line at a time.
98. The Induction Gauntlet — Bonus mark, on the way out: the bench wants exactly 2 V out of a 80-turn coil, and the flux available to collapse through it is 250 µWb. Determine how quickly that flux must collapse.